kW to Amps Motor Calculator

Pre-configured for three-phase AC circuits. Adjust values below.

Calculator InputLive calculation
Conversion Result
Enter values to calculate
Formula Used
Watts
Milliamps
Horsepower
BTU/hr

How kW to Amps Motor Works

1

Enter the motor power in kW

Use the nameplate kW rating. If the motor is rated in HP, convert: 1 HP = 0.746 kW.

2

Enter the supply voltage

Check the motor nameplate for voltage rating. Common values: 220V, 380V, 400V, 415V, 440V, 480V.

3

Enter the power factor

Motor PF is shown on the nameplate. Typical values: 0.80 at full load for small motors, 0.85–0.90 for large motors.

4

Read the full-load amps (FLA)

This is the current the motor draws at full mechanical load. Use this for cable sizing, starter selection, and overload relay settings.

kW to Amps Motor Formula

3-Phase MotorI = (kW × 1000) ÷ (√3 × V × PF)

Standard formula for three-phase induction motors.

From HPI = (HP × 746) ÷ (√3 × V × PF × η)

Includes motor efficiency (η). Typical η: 0.85–0.95.

Starting CurrentI_start ≈ FLA × 6 to 8

Induction motors draw 6–8× full-load amps during starting (DOL start).

The motor kW to amps formula is I = (kW × 1000) ÷ (√3 × V × PF) for three-phase motors.

For example, a 7.5 kW motor at 415V with PF 0.85 draws: I = (7.5 × 1000) ÷ (1.732 × 415 × 0.85) = 12.28 amps at full load.

Motor current calculations are essential for selecting the correct overload relay, contactor, cable size, and circuit breaker. The NEC requires that motor branch-circuit conductors be sized at 125% of the motor full-load current (NEC 430.22).

Frequently Asked Questions

A 5.5 kW three-phase motor at 415V with PF 0.85 draws 9.00 amps at full load.

FLA is the current a motor draws when delivering its rated mechanical output at rated voltage. It is listed on the motor nameplate.

Multiply HP by 0.746. Example: 10 HP = 7.46 kW. Then use the kW to amps formula.

At startup, the rotor is stationary and presents very low impedance, causing high inrush current (6–8× FLA). As the motor accelerates, current drops to the FLA value.

Motor PF drops at partial load. At 50% load, PF may be 0.65–0.75. At 25% load, PF may drop to 0.50–0.60. VFDs can improve partial-load efficiency.