kW to Amps Motor Calculator
Pre-configured for three-phase AC circuits. Adjust values below.
How kW to Amps Motor Works
Enter the motor power in kW
Use the nameplate kW rating. If the motor is rated in HP, convert: 1 HP = 0.746 kW.
Enter the supply voltage
Check the motor nameplate for voltage rating. Common values: 220V, 380V, 400V, 415V, 440V, 480V.
Enter the power factor
Motor PF is shown on the nameplate. Typical values: 0.80 at full load for small motors, 0.85–0.90 for large motors.
Read the full-load amps (FLA)
This is the current the motor draws at full mechanical load. Use this for cable sizing, starter selection, and overload relay settings.
kW to Amps Motor Formula
Standard formula for three-phase induction motors.
Includes motor efficiency (η). Typical η: 0.85–0.95.
Induction motors draw 6–8× full-load amps during starting (DOL start).
The motor kW to amps formula is I = (kW × 1000) ÷ (√3 × V × PF) for three-phase motors.
For example, a 7.5 kW motor at 415V with PF 0.85 draws: I = (7.5 × 1000) ÷ (1.732 × 415 × 0.85) = 12.28 amps at full load.
Motor current calculations are essential for selecting the correct overload relay, contactor, cable size, and circuit breaker. The NEC requires that motor branch-circuit conductors be sized at 125% of the motor full-load current (NEC 430.22).
Frequently Asked Questions
A 5.5 kW three-phase motor at 415V with PF 0.85 draws 9.00 amps at full load.
FLA is the current a motor draws when delivering its rated mechanical output at rated voltage. It is listed on the motor nameplate.
Multiply HP by 0.746. Example: 10 HP = 7.46 kW. Then use the kW to amps formula.
At startup, the rotor is stationary and presents very low impedance, causing high inrush current (6–8× FLA). As the motor accelerates, current drops to the FLA value.
Motor PF drops at partial load. At 50% load, PF may be 0.65–0.75. At 25% load, PF may drop to 0.50–0.60. VFDs can improve partial-load efficiency.